Español  Español | english  Français
Water Sampling Station PM 03
 
 

Water Sampling Station PM 03

Water Values – Valuable Water

The water sampling station PM 03 fulfils all the requirements of the measuring and control technology in pressurised water networks. It is thereby used for the determination and control of the chlorine/chlorine dioxide concentration in water treatment. Thus the instrument table is used in many applications. The PM 03 is perfectly suited for use in warm water networks with temperatures up to 60 °C and pressure up to 6 bar. All of the water sampling stations’s temperature and pressure-loaded components are made from high quality materials.

 

Water Sampling Station PM 03

 
  • Measurement of free chlorine or chlorine dioxide with potentiostatic measuring cell
  • Measurement of pH value or Redox
  • Clearly arranged format that is sure to function
  • Pressure-resistant to 6 bar
  • Temperatures up to 60 °C
  • Pipe installation and cabling is done by the factory
  • Possible recirculation of test water in the mains

Click to Enlarge Image

 
 
 
 
 
Measuring range free chlorinemg/l up to 10
Measuring range chlorine dioxidemg/l up to 2
Measuring range pH 0...14
Measuring range redoxmV 0...1000
Dimensions (W x H x D)mm 490 x 900 x ~100
Temperature°C 5...60
Sample water requirementl/h approx. 45
Water pressurebar 0.2...6.0
Hydraulic connections G 1/4 inner thread

Subject to technical changes

   
 
   

BW: Operation instruction
PI: Product information
MB: Dimension sheet

     
 
 

Click the link to request a quote.

Lutz-JESCO America Corp.
55 Bermar Park
Rochester, NY 14624
Toll-Free: +1-800-554-2762
Fax: +1-585-426-4025
mail@jescoamerica.com

 

Outside the U.S.
Tel.: +1-585-426-0990

1753