EASYPRO
 
   

Water sampling station EASYPRO

 
   

Reliable and individual


Designed to meet your every need, the EASYPRO system monitors and controls a range of water parameters in your industrial application. The TOPAX® MC multi-channel controller installed in the EASYPRO subjects the water parameters to constant measurement, keeping them within the target range. It enables you to control a large number of actuators and permits easy and intuitive operation. The multi-coloured LEDs provide an optical warning if the water parameters leave the target range. Automatic continuous recording of the water parameters and depiction of their de-velopment permit simple diagnosis.  

    EASYPRO components (fitted on the baseplate)
  • TOPAX® MC multi-channel controller
  • Measuring cells and measuring cell fittings
  • Sample water filter
  • Flow control
  • Flow controller DFR 45 with sampling water extraction point and installed temperature sensor
  • Inflow and outfl ow tap
  • Bracket for buffer solutions and buffer solutions for adjusting the measuring cells
  • Multi-coloured LEDs
  • Cover
  • The measuring cells are partially packaged separately and not pre-installed.

For more information please visit our website www.topax-mc.de/en

 

More product views

 
 
 
   
 

EASYPRO for industrial applications 1 2 3 4 1/1 2/2
Dimensions
(W x H x D)
with covermm 500 x 530 x 117 approx. 500 x 933 x 128 approx. - -
without covermm 490 x 490 x 117 approx. 490 x 900 x 117 approx. 900 x 490 x 117 approx. 900 x 490 x 117 approx.
Sample water requirementWith CS120 excess chlorine measuring celll/h 45 approx. -
With all other measuring cells 30 approx. 2 x
30 approx.
Sample water inflow and discharge PE hose 6/8 + stop valve with G1/4 connection
Pressure resistanceWith diaphragm-covered measuring cellbar max. 6, air gap required
With all other measuring cells max. 6
Pressure loss in the water sampling stationbar 0,3 approx.
Mesh size sample water filterµm 300
Voltage supply 100 – 240 V AC, 50/60 Hz
Power consumptionW max. 20
Analogue outputs for remote transmission 4 x 0/4 – 20 mA, working resistance max. 500 Ω
Disturbance variable inputmA 0/4 – 20
Interfaces Ethernet TCP/IP or RS485 Modbus RTU (optional)
Protection class IP65 (electronic controller)
Ambient temperature°C -5 to +45 (no exposure to direct sunlight)
Control characteristic P, PI, PID or PD behaviour, control direction selectable with disturbance variable feed forward, 2-side control selectable
v inputs (depending on version)
Number of measuring inputs 1 2a) 3b) 4c) 2 x 1 2 x 2a)
BromineDiaphragm-covered measuring cellmg/l 0 – 5e) -
Free chlorineAmperometric 3-electrode measuring cell with potentiostat (DMZ3.1)mg/l
0 – 15d)

2 x
0 – 15d)
CS120 excess chlorine measuring cellmg/l 0 – 10d) -
Diaphragm-covered measuring cellmg/l 0 – 10e) -
Chlorine dioxideAmperometric 3-electrode measuring cell with potentiostat (DMZ3.1)mg/l
0 – 15d)
-
CS120 excess chlorine measuring cellmg/l 0 – 10d) -
Diaphragm-covered measuring cellmg/l 0 – 2e) -
Total chlorineDiaphragm-covered measuring cellmg/l 0 – 10e)) -
OzonMembranbedeckte Messzellemg/l 0 – 2e) -
pH valuepH single-rod measuring cellpH 2 – 12f) or 0 – 14f) 2 x
2 – 12f) or
2 x 0 – 14f)
Redox valueRedox single-rod measuring cellmV 0 – 1000 2 x
0 – 1000
Conductivity conductiveConductivity measuring cell (k=1)mS/cm 0 – 2g), 0 – 20g) oder 0 – 100g) 2 x 0 – 2g),
0 – 20g) oder
0 – 100g)
ChloriteDiaphragm-covered measuring cellmg/l 0 – 2e) -
Hydrogen peroxideDiaphragm-covered measuring cellmg/l 0 – 200e) -
TemperaturePt100°C 5 – 45 (standard version)
5 – 60 (can be configured via the Matchcode ordering system)
Output modules (depending on version)
Number of output modules up to 4 2 x up to 4
Servomotor relay 2 x 230 V AC, 5 A (ohmic load)
Potentiometer feedback: 1 – 10
Servomotor 20 mA Constant 0/4 – 20 mA output
Servomotor with 20 mA feedback
Relay 2 x 230 V AC, 5 A (ohmic load)
Optocoupler 2 x 80 V DC, 5 mA
         

a) A temperature sensor can also be connected.
b) Additionally, up to two temperature sensors can be connected.
c) Additionally, up to three temperature sensors can be connected.
d) Dependant on the measuring cell transconductance.
e) Depandant on the measuring cell.
f) Depandant on the single-rod measuring cell.
g) Depending on the configuration, corresponds to approx. 0 – 1 % or 0 – 5 % salt content.
Subject to technical changes.

   
 
     
 
 

Click the link to request a quote.

Lutz-JESCO America Corp.
55 Bermar Park
Rochester, NY 14624
Toll-Free: +1-800-554-2762
Fax: +1-585-426-4025
mail@jescoamerica.com

 

Outside the U.S.
Tel.: +1-585-426-0990

3239